Non-Metallic Fire Door Applications
ve |
|
Thermalguard Technology TG-1000 and TG-2000 Resin Systems and TG-600 Coating Systems Fire Zone Door Screening Tests |
|
Test Protocol
1. Screening Test based upon UL 1709 2. Test Duration: 30 Minutes 3. Testing Configuration Thickness 4mm Composite-2.5cm Core-4mm Composite 4. Flame Impingement Temperature: 1,100⁰C (2,000⁰F) 5. Criteria: Back Face Temperature cannot exceed 121⁰C (250⁰F) |
|
Results after 35 minutes of testing:
1. Starting Front Surface Temperature 21⁰C 2. Finishing Back Surface Temperature-Worst Case: 44⁰C Best Case: <30⁰C 3. No Burn Through!!
|
|